What is the difference between CMR and CMP Ethernet cable?
CMR cable is listed for riser applications, where a vertical pathway could carry fire between floors. CMP cable has plenum fire and smoke characteristics for ducts and other spaces used for environmental air. The space and local code determine which listing is required; neither rating makes the cable faster or automatically suitable outdoors.
What CMR means
CMR identifies communications cable listed with fire-resistant characteristics for vertical riser installations. It is commonly specified for runs between floors through risers or shafts.
The rating is about limiting fire spread, not bandwidth. A Cat6 CMR cable and Cat6 CMP cable can have the same network category while using different jacket constructions.
What CMP means
CMP identifies plenum-rated communications cable designed to restrict flame propagation and limit smoke under the applicable test. It is used in ducts, plenums and other spaces that circulate environmental air, which can include some suspended-ceiling or raised-floor spaces.
A suspended ceiling is not automatically a plenum, and a home attic is not automatically one either. Determine how the space is actually used before selecting the cable.
Do not choose by room name alone
The authority having jurisdiction and the adopted code determine the acceptable listing for the route. Building type, fire-rated assemblies and whether the space handles air can all change the answer.
Penetrations through fire-rated construction also need an appropriate firestop system. Buying CMP cable does not replace fire-stopping or other code requirements.
CM, CMR, CMP and outdoor ratings are not interchangeable labels
CM is a general communications listing, while CMR and CMP address particular fire exposures. Outdoor, CMX and OSP products address different conditions such as moisture or sunlight exposure.
Check the full product datasheet for every part of the route. A plenum jacket is not a substitute for water blocking, UV resistance or direct-burial construction.
What to put in a quote
Ask for the manufacturer, part number, category and jacket listing, plus any required fire-stopping and the inspection responsibility. That makes the material choice reviewable and prevents a generic phrase such as in-wall cable from hiding the wrong product.
Sources and further reading
Best for
Choosing cable for risers, air-handling spaces or other concealed routes.
Things to consider
- The space determines the required listing
- Fire-stopping is a separate requirement
- Outdoor suitability needs its own rating
Common mistakes
- Assuming every suspended ceiling is a plenum
- Choosing by room name instead of the actual air pathway
What we recommend
Confirm the route and local code, then put the exact cable listing and part number in the quote.